Fire Alarm Control Panel
Fire Alarm Control Panel 5 ZONE, 10 ZONE
Features
  • Alarm Verification: To avoid false alarm from environment interference and unstable pulse. On receiving a fire signal from detector or manual call point, Panel accumulates the fire signal before Alarm Verification time: 12 seconds, if the fire signal is still existing, Panel start to alert.
  • Zone test: Alarm and Fault function test.
  • Back up battery test.
  • Fault indications for wire disconnection, unstable AC power, battery short circuit or disconnection and fuse trouble.
  • Different sounds to indicate fire alarm or disconnection.
  • Annunciator is available to connect with.
Specification
Model HC-5AL HC-10AL
Total Loops 5 Loops 10 Loops
Input Power 220VAC 50/60Hz
Aux. Power (Spare Battery) DC 24V 300mAH (NI-Cd Battery) DC 24V 600mAH (NI-Cd Battery)
Charging Voltage/Current DC 29V 60mA
Loop Valtage, Current Nomal: DC24V, Short-Circuit: 5V, Under 30mA
Exterio Resistance Round-trip under50Ω
Amount of Smoke Detectors Max. Amount of Connection: 20/ Loop
Amount of Heat Detectors No Limit (Except Electronic Type)
End of Line Resistance 10KΩ
Output Current for Indicating Lamp Max. Output Current: 120mA Max. Output Current: 240mA
Output Current for Alam Bell Max. Output Current: 120mA Max. Output Current: 240mA
Case Material ABS resin with non-flammability
Auxiliary Contact 1 Null-Valtage Contact (N/O, 250VAC, 7A)