Home > Products > Fire Alarm Control Panel
Fire Alarm Control Panel
Features
- Alarm Verification: To avoid false alarm from environment interference and unstable pulse. On receiving a fire signal from detector or manual call point, Panel accumulates the fire signal before Alarm Verification time: 12 seconds, if the fire signal is still existing, Panel start to alert.
- Zone test: Alarm and Fault function test.
- Back up battery test.
- Fault indications for wire disconnection, unstable AC power, battery short circuit or disconnection and fuse trouble.
- Different sounds to indicate fire alarm or disconnection.
- Annunciator is available to connect with.
Specification
Model | HC-5AL | HC-10AL |
Total Loops | 5 Loops | 10 Loops |
Input Power | 220VAC 50/60Hz | |
Aux. Power (Spare Battery) | DC 24V 300mAH (NI-Cd Battery) | DC 24V 600mAH (NI-Cd Battery) |
Charging Voltage/Current | DC 29V 60mA | |
Loop Valtage, Current | Nomal: DC24V, Short-Circuit: 5V, Under 30mA | |
Exterio Resistance | Round-trip under50Ω | |
Amount of Smoke Detectors | Max. Amount of Connection: 20/ Loop | |
Amount of Heat Detectors | No Limit (Except Electronic Type) | |
End of Line Resistance | 10KΩ | |
Output Current for Indicating Lamp | Max. Output Current: 120mA | Max. Output Current: 240mA |
Output Current for Alam Bell | Max. Output Current: 120mA | Max. Output Current: 240mA |
Case Material | ABS resin with non-flammability | |
Auxiliary Contact | 1 Null-Valtage Contact (N/O, 250VAC, 7A) |